General data

-Standards:

BG-GS-ET-14

BG-GS-ET-20

EN IEC 62061

EN ISO 13849-1

EN IEC 60947-5-1

EN IEC 60947-5-3

EN IEC 60947-5-5

EN IEC 60204-1

EN IEC 60947-1

Climatic stress

-EN 60068-2-3

-BG-GS-ET-14

Housing material

-Glass-fibre reinforced thermoplastic, ventilated

Gross weight

-164 g

General data - Features

-Wire breakage detection

-Automatic reset function

-Reset after disconnection of supply voltage

-Integral system diagnostics, status

-Number of LEDs: 1

-Number of normally closed (NC): 4

-Number of normally open (NO): 2

-Number of safety contacts: 1

Safety classification

Standards:

-EN ISO 13849-1

-EN IEC 61508

Safety classification - Relay outputs

-Performance Level, up to: c

-Category: 1

-PFH value: 1.14 x 10⁻⁶ /h

-Notice: for max. 50,000 switching cycles/year and max. 80% contact load

-Safety Integrity Level (SIL), suitable for applications in: 1

-Mission time: 20 Year(s)

Mechanical data

-Mechanical life, minimum: 3,000,000 Operations

-Mounting: Snaps onto standard DIN rail to EN 60715

Mechanical data - Connection technique

-Terminal designations: IEC/EN 60947-1

-Termination:

-Rigid or flexible

-Screw terminals M20 x 1.5

-Cable section, maximum: 2.5 mm²

-Tightening torque of Clips: 0.6 Nm

Mechanical data - Dimensions

-Width: 22.5 mm

-Height: 75 mm

-Depth: 110 mm

Ambient conditions

-Degree of protection of the enclosure: IP40

-Degree of protection of the mounting space: IP54

-Degree of protection of clips or terminals: IP20

-Ambient temperature: +0 ... +55 °C

-Storage and transport temperature: -25 ... +70 °C

-Resistance to vibrations: 10...55 Hz, Amplitude 0.35 mm, ± 15 %

-Restistance to shock: 30 g / 11 ms

Ambient conditions - Insulation values

-Rated impulse withstand voltage Uimp: 4 kV

-Overvoltage category: III

-Degree of pollution: 2

Electrical data

-Frequency range: 50 Hz, 60 Hz

-Thermal test current: 4A

-Rated operating voltage: 110 VAC

-Rated AC voltage for controls, 50 Hz, minimum: 93.5 VAC

-Rated control voltage at AC 50 Hz, maximum: 121 VAC

-Rated AC voltage for controls, 60 Hz, minimum: 93.5 VAC

-Rated control voltage at AC 60 Hz, maximum: 121 VAC

-Electrical power consumption: 2.4 W

-Contact resistance, maximum: 0.1 Ω

-Note (Contact resistance): in new state

-Drop-out delay in case of power failure, typically: 80 ms

-Drop-out delay in case of emergency, typically: 20 ms

-Pull-in delay at automatic start, maximum, typically: 100 ms

-Pull-in delay at RESET, typically: 20 ms

-Material of the contacts, electrical: AgCdO

Electrical data - Safe relay outputs

-Voltage, Utilisation category AC-15: 250 VAC

-Current, Utilisation category AC-15: 1.5 A

-Voltage, Utilisation category DC-13: 24 VDC

-Current, Utilisation category DC-13: 1A

-Switching capacity, minimum: 10 VDC

-Switching capacity, minimum: 10 mA

-Switching capacity, maximum: 250 VAC

-Switching capacity, maximum: 8A

Electrical data - Digital inputs

-Conduction resistance, maximum: 40 Ω

Electrical data - Digital Output

-Voltage, Utilisation category DC-12: 24 VDC

-Current, Utilisation category DC-12: 0.1 A

Electrical data - Relay outputs (auxiliary contacts)

-Switching capacity, maximum: 24 VDC

-Switching capacity, maximum: 2A

-Electrical data - Electromagnetic compatibility (EMC):

-EMC rating: EMC-Directive

Status indication

-Indicated operating states: Authorised operation

Other data

-Note (applications): Safety sensor, Guard system