Product Information:
- Product line: MCCB TS
- Origin: LS Korea
- Standard : IEC 60947-2
- Tuning feature: The product is capable of adjusting the short-circuit cut-off current with 9 different setting levels, allowing to customize the protection level in accordance with system requirements.
- Design and quality: The circuit breaker has a compact and high-quality design, which saves space and ensures stable performance.
- Material: The product is made from high-quality materials, with fire resistance.
- Safe and friendly: The product is designed to be safe and user-friendly, minimizing risks related to electricity.
- Easy installation, operation and maintenance: The circuit breaker is easy to install, operate and maintain, and can replace accessories conveniently
Specifications:
Rated current | 500A |
Pole | 4P |
Rated insulation voltage(Ui) | 1000V |
Rated Impulse Voltage(Uimp) | 8kV |
Rated extreme short-circuit power, (kA) (Icu) | 50KA |
Rated operating voltage (V) | 380V/415V |
Categories of use | A |
Heat | Io, Ir | ETS: Ir = 0.4~1.0×In (13settings) |
ETM: Io = 0.5~1.0×In (6settings) lr = 0.8~1.0×Io (5settings) |
p(6Ir) | ETS: 6sec at 6Ir (fixed) |
ETM: 12sec at 6Ir (5settings) |
Now | Glass | ETS, ETM: 1.5~10×Ir (9settings) |
Lt | 12×In |
Neutral protection | 4P3d | No protection |
4P3D+N/2 | 0.5×Ir |
4P4d | 1.0×Ir |
Cable | Min | 70mm2 (160A) |
Max | 185mm2 ×2 / 350 kcmil×2 (630A |
MCCB (W×H×D) | 186.5×260×110 |
Product structure:
Product Size :
Wiring diagram :
Application:
- Overload Protection: MCCB is used to protect equipment and cables from overload, when the current exceeds the permissible limit for an extended period of time.
- Short Circuit Protection: MCCB breaks the circuit quickly when a short circuit occurs in the electrical system, preventing possible fires and fires.
- Ground Fault Protection: Some types of MCCBs have built-in leakage protection, helping to break the circuit when an electrical leak occurs, ensuring safety for people and property.
- Current control and regulation: MCCB can be used to control and regulate the current in the electrical system.
- Cut-off for electrical appliances: MCCB is used as an electrical switch to disconnect and connect current to electrical equipment such as machinery, motors, lamps, etc.
- Lightning protection: MCCB can be used to protect the system from the effects of lightning and create a protective layer for electrical equipment.
- Use in power distribution systems: MCCBs are used in main power distribution systems to cut off power when necessary to protect the entire system.
- Overvoltage Protection: Some MCCBs have built-in overvoltage protection, which prevents equipment and systems from unwanted pressure fluctuations.