SKU: TS630N FMU630 3P 630A
Name of Series: MCCB/ELCB LS Series
Manufacturer: LS
Category: MCCB
+

Related products

Product Information:

            - Product line: MCCB TS

- Origin: LS Korea

- Standard : IEC 60947-2

- Tuning feature: The product is capable of adjusting the short-circuit cut-off current with 9 different setting levels, allowing to customize the protection level in accordance with system requirements. 

- Design and quality: The circuit breaker has a compact and high-quality design, which saves space and ensures stable performance.

- Material: The product is made from high-quality materials, with fire resistance.

- Safe and friendly:  The product is designed to be safe and user-friendly, minimizing risks related to electricity.
- Easy installation, operation and maintenance: The circuit breaker is easy to install, operate and maintain, and can replace accessories conveniently

Specifications:

Rated current

630A

Pole

3P

Rated insulation voltage(Ui)

1000V

Rated Impulse Voltage(Uimp)

8kV

Rated extreme short-circuit power, (kA) (Icu)

50KA

Rated operating voltage (V)

380V/415V

Categories of use

A

Heat

Io, Ir

ETS: Ir = 0.4~1.0×In (13settings)
ETM: Io = 0.5~1.0×In (6settings)
lr = 0.8~1.0×Io (5settings)

p(6Ir)

ETS: 6sec at 6Ir (fixed)
ETM: 12sec at 6Ir (5settings)

Now

Glass

ETS, ETM: 1.5~10×Ir (9settings)

Lt

12×In

Neutral protection

4P3d

No protection

4P3D+N/2

0.5×Ir

4P4d

1.0×Ir

Cable

Min

70mm2 (160A)

Max

185mm2 ×2 / 350 kcmil×2 (630A

MCCB (W×H×D)

186.5×260×110

Product structure:

Cau-tao-san-pham-TS.jpg

Product Size :

kich-thuoc-san-pham-TS.jpg

Wiring diagram :

so-do-ket-noi-TS.jpg

Application:

- Overload Protection: MCCB is used to protect equipment and cables from overload, when the current exceeds the permissible limit for an extended period of time.

- Short Circuit Protection: MCCB breaks the circuit quickly when a short circuit occurs in the electrical system, preventing possible fires and fires.

- Ground Fault Protection: Some types of MCCBs have built-in leakage protection, helping to break the circuit when an electrical leak occurs, ensuring safety for people and property.

- Current control and regulation: MCCB can be used to control and regulate the current in the electrical system.

- Cut-off for electrical appliances: MCCB is used as an electrical switch to disconnect and connect current to electrical equipment such as machinery, motors, lamps, etc.

- Lightning protection: MCCB can be used to protect the system from the effects of lightning and create a protective layer for electrical equipment.

- Use  in power distribution systems: MCCBs are used in main power distribution systems to cut off power when necessary to protect the entire system.

- Overvoltage Protection: Some MCCBs have built-in overvoltage protection, which prevents equipment and systems from unwanted pressure fluctuations.